3-Phase Active Front End Module - Liquid Cooled

AFE 33kW – Scalable to 1MW total system power

Description

The AFE333KLQ is a non-isolated fully integrated 3-phase active front end power module with liquid cooling that is suitable for use as a bidirectional grid connected rectifier in systems for renewable energy, battery chargers, energy storage and general-purpose converters.

The AFE333KLQ takes a 3-phase AC input voltage and converts it into a high voltage DC output. It will control the input power factor to a specified level and allows independent control of both active and reactive current
or power.

In addition, it supports bidirectional power flow with a seamless transition between delivery of power to and from the AC grid. Furthermore, it offers a choice of different control modes including direct active/reactive power control, direct active/reactive current control and DC output voltage control.

The AFE333KLQ offers a large power density with a DC power level of 33kW in a half-width 19” module with a height of only 5RU. Up to 32 units can be paralleled in a master-slave system for a maximum system power level of more than 1MW.

Features

Typical/Recommended Operating Conditions

Parameter

Grid Voltage (L-L)

Grid Current

Grid Frequency

Grid Voltage Phase Imbalance (*1)

DC Voltage Range

DC Current

Operating Temperature Range Ambient Air Full Power (*1)

Operating Temperature Range Liquid Full Power (*1)

AUX Power Supply Input Voltage

AUX Power Supply Input Current

Grid Power Factor (controllable via comm. interface)

Grid Current THD (at full power)

DC Voltage Accuracy (from setpoint)

Peak Efficiency

Idle Apparent Power (not connected to Grid)

Standby Active Power (connected to grid, power factor set to unity)

Standby Reactive Power (connected to grid, power factor set to unity)

Min

360

47

600

-47

-35

-35

20

0

0.9 lagging

-0.5

Max

530

57

63

3

900

47

70

60

27

700

0.9 leading

5

+0.5

98.2

1

50

100

Unit

Vrms

Arms

Hz

%

Vdc

A

°C

V

V

mA

%

%

%

VA

W

VAr

Note 1: Derate output power above maximum level. Unit will shut down when exceeding absolute maximum rating(s).

Protection Features

  • High
  • Low
  • Phase imbalance

Normative

Approvals

CE Approval Directives:

UL Approval upon request.

Safety

EMC

Grid Codes

To ensure compliance with local grid codes, the use of an externally connected grid protection relay is required.

For complete set of specifications, please request the datasheet below.